小型制药冷冻干燥机日常维护和保养!
Check Before Running: 每次开机前要例行检查
ü The state of various valves (absorbing, exhausting valves for compressors, service valves, capped valves and etc.)
所有截止阀(压缩机吸、排气阀、供液阀、手阀等)处于开启状态;
ü Pressure meter: 0.6~0.7Mpa
压力表正常读数:0.6~0.7Mpa
ü Level of compressor oil: 1/4~3/4
压缩机正常油位:1/4~3/4;
After Power Supply, Please Notice: 送电后应注意
ü Whether compressor collects the refrigerant
压缩机是否自动收液;
ü Whether difference-oil pressure resets
油压差是否复位等;
After Running, Please Notice: 开机后注意
ü Whether the sound of compressor is normal, if not, please check power supply
压缩机运行声音是否正常,如果异常请先检查供电的三相电是否平衡;
ü Whether the refrigerating piping vibrates normally, if yes, please fix the loosen parts
制冷管路是否有异常振动,如果有则采用相应的固定措施;
ü Whether the flux of refrigerant is normal by observing the sight glass, if having bubble in sight glass, please check the content of refrigerant and thermostatic valves
视液镜流量是否正常,若有气泡,则说明制冷剂缺少或膨胀阀流量太大;
ü The state of frosting on the thermostatic valves
膨胀阀结霜情况;
ü The state of frosting on the compressor
压缩机回霜情况;
ü Compressor oil return, generally, 1/3~3/4
冷冻油的回油情况;(一般保持在油视镜的1/3~3/4)
Compressor Start-up: 压缩机启动
ü Start frequently as little as possible, internal more than 3min
不能频繁启动,间隔的时间应大于3min;
上海拓纷机械设备有限公司{搜索公司名即可找到我们}
版权与免责声明:凡本网注明“来源:兴旺宝网”的所有作品,均为浙江兴旺宝明通网络有限公司-兴旺宝网合法拥有版权或有权使用的作品,未经本网授权不得转载、摘编或利用其它方式使用上述作品。已经本网授权使用作品的,应在授权范围内使用,并注明“来源:兴旺宝网”。违反上述声明者,本网将追究其相关法律责任。 本网转载并注明自其它来源(非兴旺宝网)的作品,目的在于传递更多信息,并不代表本网赞同其观点或和对其真实性负责,不承担此类作品侵权行为的直接责任及连带责任。其他媒体、网站或个人从本网转载时,必须保留本网注明的作品第一来源,并自负版权等法律责任。 如涉及作品内容、版权等问题,请在作品发表之日起一周内与本网联系,否则视为放弃相关权利。