Analog Input | |||
Input Channel | 8 Differential | ||
Input Type | -20 mA ~ +20 mA, 0 mA ~ +20 mA, +4 mA ~ +20 mA | ||
Resolution | Normal Mode | 16-bit | |
Fast Mode | 12-bit | ||
Sampling Rate | Normal Mode | 16-bit, 10 Samples/Sec. (Total) | |
Fast Mode | 12-bit, 60 Sample/Sec. (Total) | ||
Accuracy | Normal Mode | +/-0.1% of FSR | |
Fast Mode | +/-0.5% of FSR | ||
-3dB Bandwidth | Normal Mode | 15.7 Hz | |
Fast Mode | 78.7 Hz | ||
Zero Drift | +/-20 μV/°C | ||
Span Drift | +/-25 ppm/°C | ||
Common Mode Rejection | 86 dB | ||
Normal Mode Rejection | 100 dB | ||
Input Impedance | 125 Ω | ||
Common Voltage | +/- 200 VDC | ||
Individual Channel Configurable | Yes | ||
Open Wire Detection for 4 ~ 20 mA | Yes | ||
Intra-module Isolated, Field-to-Logic | 3000 VDC | ||
ESD Protection | +/-4 kV Contact for Each Channel |
ZB-2017C-T CR | Wireless 8-ch Current Input Module with High Common Voltage Protection (RoHS) |
Important Note: The Zigbee Data Acquisition modules need a Zigbee host converter to coordinate the data transmission route. Please remember to order a ZB-2550, ZB-2550-T, ZB-2550-PA, ZB-2570, ZB-2570-T or ZB-2570-PA ZigBee host converter when you purchase the Zigbee Data Acquisition products. |
MDR-20-24 | 24 VDC/1.0 A, 24 W Power Supply with DIN-Rail Mounting |
ZB-2510-T CR | ZigBee Repeater (RoHS) (CE/FCC) |
ZB-2010-PA CR | High Power Amplifier ZigBee Repeater (RoHS) |
ZB-2550-T CR | RS-485/RS-232 to ZigBee Converter (Host) (RoHS) |
ZB-2550-PA CR | RS-485/RS-232 to High Power Amplifier ZigBee Converter (Host) (RoHS) |
ZB-2570-T CR | Ethernet/RS-485/RS-232 to ZigBee Converter (Host) (RoHS) |
ZB-2570-PA CR | Ethernet/RS-485/RS-232 to High Power Amplifier ZigBee Converter (Host) (RoHS) |