品牌
其他厂商性质
合肥市所在地
微机消谐装置
RC-XX-1/2
使
用
说
明
书
合肥睿驰电气科技有限公司
目 录
一、产品概述················································································· 1
1 概述····················································································· 1
2 功能及特点········································································ 2
3.信号灯及按键说明······················································· 3
4 工作原理············································································· 4
二、操作说明················································································· 5
三、使用环境··············································································· 10
四、装置端子接线图·································································· 10
五、安装尺寸··············································································· 12
六、通讯规约··············································································· 13
一、产品概述
1. 概述
该产品将微机技术用于电网消谐,利用计算机快速、准确的数据处理能力实现快速傅里叶分析,其选频准确。通过对PT电压的采集,对电网谐振时的各种频率成份能快速分析,准确的辨别出:接地故障、过压故障和谐振故障。
如果是电网谐振,微机控制器发出指令使消谐电路投入,实现快速消谐。本装置对各种高频、低频和工频谐振均准确判断,动作迅速,较完善地解决了电力系统中电网的消谐问题,并能记录发生的故障以及故障发生的时间。本装置可广泛应用于发电厂、变电站及钢铁、煤炭、石油化工等大型厂矿企业的电力系统。
2. 功能及特点
u 模块化设计,结构紧凑,技术*,高速DSP核处理器使运算实时性和动作准确性得以保证;
u 实时监控系统状态,对出现的异常运行状态(接地故障、过压故障和电网谐振)做出准确判断,并作出及时动作;
u 工业标准的RS-485通讯接口,可以向上位机传送系统的运行状态;
u 故障追忆功能,显示最近20次历史故障记录;
u 具有良好的电磁兼容性,适合在强电磁干扰的复杂环境中应用;
u 双硬件看门狗电路确保软件运行的可靠性;
u 中文液晶显示,运行状态清晰,菜单式操作,方便易用。
3.信号灯及按键说明:
u 运行: 正常运行指示灯,闪烁频率1Hz;
u 谐振: 谐振故障指示,谐振故障消除后熄灭;
u 报警: 故障指示,系统正常运行后熄灭;
u ←↑↓→:菜单选择和参数调整按键;
u 确认: 进入下级菜单和确认参数设定按键;
u 取消: 返回上级菜单和取消参数设定按键;
u 复位: 系统重新启动按键。
4.工作原理
该产品是基于PT提供的开口电压信号而设计的产品。装置总体结构如下图所示:主要由微处理器、按键显示、信号输出和电源等模块构成。
二、操作说明
设备在到达现场后,*行控制器试验。
1. 通电开机后液晶屏显示:
消谐控制器
|
2.2秒后显示界面:
运 行
05-06-11-10-00 |
当装置上电后,将显示“运行”、两段母线运行状态和当前时间。当系统出现接地故障、过压故障、和电网谐振故障时,将会显示报警,如下图所示:
运 行 接地故障 08-09-30-10-00 |
3.按下“确认”按键进入主菜单界面:
主菜单 故障追忆 时间设定 站号设置 |
通过“↑↓”按键选择操作项目,选定项为反色显示。按下“确认”可进入要操作的子菜单界面。主菜单共有5项,还有2项如下图:
主菜单 参数设置 版本信息
|
4.故障追忆
故障追忆 序号:07 工频谐振 05-09-27-10-48 |
通过“↑↓”按键查询最近20次故障的历史记录。按下“取消”返回主菜单界面。
5.时间设定
时间设定 05-06-29-10-48
|
通过按“±”按键选择修改时间参数(选中项反色显示),“↑↓”按键来修改时间,显示的时间依次为“年-月-日-时-分”,“确认”按键保存新设置的时间并返回主菜单,“取消”按键不保存新设置的时间并返回主菜单。
6.站号设置
站号设置 站号:01
|
通过按“±”按键选择修改站号参数(选中项反
色显示),“↑↓”按键来修改站号,“确认”按键保存新设置的站号并返回主菜单,“取消”按键不保存新设置的站号并返回主菜单。
7.参数设置
在参数设置前需要输入密码,如果密码正确才能修改参数,否则返回主菜单界面。出厂设定密码“99”。输入密码界面:
输入密码10
|
通过按“±”按键,输入密码,密码正确后,进入参数设置界面:
三分频 30V 二分频 30V 工 频 150V 三倍频 150V |
“↑↓”按键选择修改参数的项目,选中项目反色显示,“±”按键设置参数数值,“确认”按键保存新设置的站号并返回主菜单,“取消”按键不保存新设置的站号并返回主菜单。
8.版本信息
版本信息 V2.0 |
按下“取消”返回主菜单界面。
三、使用环境
1. 海拔高度:小于2000m,特殊情况下可达4000m;
2. 工作环境温度:-10℃- 60℃;
3. 空气相对湿度:90% (25℃)、50% (40℃)
4. 使用地点不得有腐蚀性气体、蒸汽、导电尘埃,不得有爆炸性气体和破坏绝缘性气体;
5. 安装地点具有防风、防雨和防尘设施。
四、装置端子接线图
A B
1. 端子A为装置信号通讯:
u A15~A16为第I段母线开口电压输入;
u A9~A10 为第II段母线开口电压输入;
u A5~A6为接地公共端;
u A3为485通讯接口地;
u A2为485通讯接口A;
u A1为485通讯接口B;
2. 端子B为装置电源报警:
u B15~B16提供电源输入接口;AC/DC 85 ~265V;
u B11~B13为接地端;
u B5~B6为第I段母线故障报警端子,常开;
u B3~B4为第II段母线故障报警端子,常开;
u B1~B2为失电报警端子,常闭;
五、安装尺寸(mm) 深度:200mm
六.通讯规约
消谐MODBUS(RTU模式)通讯规约,采用RS-485, 波特率为9600BPS,1位起始位,8位数据位,无校验,1位停止位,共10位。XHG出厂时站址和通讯波特率已设好了,站址为01。
CRC校验权值为CRC-16=X16+X15+X5+1
1. 主站询问下行报文格式:
地址+功能码+起始地址+字长度+16位CRC校验码
地址 | 功能码 | 起始地址 | 数据字长度 | CRC校验码 | |||
ADD | 03H | 00H | 00H | 00H | 04H | CRC低 | CRC高 |
2. 从站应答上行报文格式:
地址+功能码+字长度+数据长度+16位CRC校验码
地址 | 功能码 | 字节长度 | 数据 | CRC校验码 | |
ADD | 03H | 08H | 8字节 | CRC低 | CRC高 |
3. 数据格式定义:
地址 | 状态定义 | 备注 |
0000H | 第I段故障属性 | =00 00H (正常) ; =00 01H (谐振故障) =00 02H (接地故障);=00 04H (过压故障); |
0001H | 第1段谐振属性 | =00 00H(正常) =00 01H(三分频) =00 02H(二分频) =00 04H(工频) =00 08H(三倍频) |
0002H | 第2段故障属性 | =00 00H (正常) ; =00 01H (谐振故障) =00 02H (接地故障);=00 04H (过压故障); |
0003H | 第2段谐振属性 | =00 00H(正常) =00 01H(三分频) =00 02H(二分频) =00 04H(工频) =00 08H(三倍频) |
例:若设备地址为1
读取状态数据:
主站发送:01 03 00 00 00 04 44 09
其中 44 09为CRC校验码
设备回应:01 03